Multiple services were experiencing issues in the europe-west2 region

Answers How did a data center with backup generators lose power?

A utility cable fault cut power to the data center behind europe-west2-b while its second feed was open for repairs. The generator controller sensed live voltage upstream of that open breaker, decided utility power was…

The problem
Utility feed A failed while feed B’s breaker was open for repairs, and the generator controller saw voltage upstream of it.
What they did
The PLC never started the generators; the team moved the load to the standby utility source, then fixed the PLC logic.
The result
europe-west2-b lost power once its UPS batteries ran out; the main impact was resolved within 6 hours and 8 minutes.

Why read it Redundant power that failed because a sensor was wired on the wrong side of a breaker.